berg - die Energieoptimierer

Gateways & Signal Converters

BCM 4 M-Bus

For combined acquisition of 4 S0 pulse counters and machine running times. The multicounter module is designed for data transmission in M-Bus format.

Features

  • Counter module with 4 separate S0 channels according to EN 62053-31
  • Communication variant: M-Bus
  • DIN-rail mounting according to IEC 60715
  • 3 TE width
  • Suitable for contacts and open collector transistors
  • Channels programmable for counting machine running times

Technical Data

Casing according to DIN 43880, material PPO self-extinguishing
Dimensions W:53 mm (3HP), H: 90 mm (incl. connector), D: 58 mm
Installation DIN profile rail according to EN 50022
Protection class IP20
Connectors S0 inputs: 1 x 8-pole screw terminals, grid dimension 5.08, bus: 2 x 2-pole screw terminals, grid dimension 3.81
Power supply 24 VDC +/- 5 %
Power consumption max. 60 mA
Inputs 4 x S0 class A according to EN 62053-31
S0-Voltage 15.5 V idle
S0-Line current 4 x ca.14 mA max.
Input IS0 > 10mA Input IS0 > 10mA
Active IS0 < 2mA
Debounce time approx. 8 msec
Temperature range -10 °C to -55 °C
Baud rates 300, 2400, 9600 bit/s (default: 2400 bit/s)
Bus load 1 Unit Load (approx. 1.5mA)
Number of logical 4M bus slaves 4
Slave-function 4 x Counter, 32Bit dual
Max. Counting frequency 50Hz
Data transfer M-Bus according to EN 1434

Variant



  • BCM 4 M-Bus   Item number: 003773 Pulse acquisition module for up to four S0 pulse counters
    and conversion of pulse readings into M-Bus protocol

BCM 8 DP

S0-ImpulserfassuS0 impulse acquisition module for transmission of consumption values from up to 8 intermediate meters into the Profibus DP protocol

Merkmale

  • Counter-Modul mit 8 separaten S0 Kanälen nach EN 62053-31
  • Kommunikationsvariante: ProfibusDP
  • DIN-Schienen Montage nach IEC 60715
  • 6 TE Breite
  • Für Kontakte und Open Kollektor Transistoren geeignet
  • Kanäle zur Zählung von Maschinenlaufzeiten programmierbar (modellabhängig)

Technical Data

Case according to DIN 43880, material PPO self-extinguishing
Dimensions W: 106 mm (6TE), H: 115 mm (incl. connector), D: 63 mm
Installation on DIN profile rail according to EN 50022
Protection Class IP20
Connections S0 inputs: 2 x 8 pin screw terminals, grid dimension 5,08, Bus: 2 x 2 pin screw terminals, grid dimension 3,81
Supply 18… 35VDC
Current consumption max. 350 mA at 24VDC
Inputs 8 x S0 class A nach EN 62053-31
S0 voltage 18V open circuit
S0 line current 8 x approx.17 mA max.
Active input IS0 > 10mA
Inactive input IS0 < 2mA
Debounce time approx. 8 msec
Temperature range  -10 °C to -55 °C
Baud rates 300, 2400, 9600 bit/s (default: 2400 bit/s)
Bus load 1 unit load (approx. 1,5mA)
Number of logical 4M bus slaves 4
Slave function 8 x counter, 32bit dual
Max. Meter frequency 50Hz
Data transmission S0 to ProfibusDP
Data interface Profibus DP, SUB-D 9pol. according to EN 50170,
Baud rates up to 12 MBaud
DP allocation 32 byte E-periphery, 32 byte A-periphery

Variant



  • BCM 8 Profibus DP   Item number: 000595 Pulse acquisition module for up to eight S0 pulse counters
    and conversion of the pulse states into the Profibus DP protocol

BCM 8 Modbus

For combined acquisition of S0 impulse counters and machine running times. The multicounter module is designed for data transmission in the ModbusRTU protocol.

Features

  • Counter module with 8 separate S0 channels according to EN 62053-31
  • Communication variant: ModbusRTU
  • DIN-rail mounting according to IEC 60715
  • 6 TE width
  • Suitable for contacts and open collector transistors
  • Channels programmable for counting machine running times (model dependent)

Technical Data

Case according to DIN 43880, material PPO self-extinguishing
Dimensions W: 106 mm (6TE), H: 115 mm (incl. connector), D: 63 mm
Installation on DIN profile rail according to EN 50022
Protection class IP20
Connections S0 inputs: 2 x 8 pin screw terminals, grid dimension 5,08, Bus: 2 x 2 pin screw terminals, grid dimension 3,81
Supply 18… 35VDC
Current consumption max. 350 mA at 24VDC
Inputs 8 x S0 class A according to EN 62053-31
S0 voltage 18V open circuit
S0 line current 8 x approx.17 mA max.
Active input IS0 > 10mA
Inactive input IS0 < 2mA
Debounce time approx. 8 msec
Temperature range  -10 °C to -55 °C
Baud rates 300, 2400, 9600 bit/s (default: 2400 bit/s)
Bus load 1 unit load (approx. 1,5mA)
Number of logical 4M bus slaves 4
Slave function 8 x counter, 32bit dual
Max. Counter frequency 50Hz
Data transmission S0 / machine run times on ModbusRTU
Data formats DWORD (32 Bit Dual), Real single precision
Baud rates 300 … 57.6k
Transmission media RS485, connection via screw terminals
Termination Fail Save, can be switched on/off via jumper

Variant



  • BCM 8 Modbus   Item number: 002639 Pulse acquisition module for up to eight S0 pulse counters
    and conversion of the pulse states into the Modbus RTU protocol.

BCM 8 M-Bus

For combined acquisition of 8 S0 impulse counters and machine running times. The multicounter module is designed for data transmission in M-Bus format.

Features

  • Counter module with 8 separate S0 channels according to EN 62053-31
  • Communication variant: M-Bus
  • DIN-rail mounting according to IEC 60715
  • 6 TE width
  • Suitable for contacts and open collector transistors
  • Channels programmable for counting machine running times (model dependent)

Technical Data

Case according to DIN 43880, material PPO self-extinguishing
Dimensions W: 106 mm (6TE), H: 115 mm (incl. connector), D: 63 mm
Installation on DIN profile rail according to EN 50022
Protection class IP20
Connections S0 inputs: 2 x 8 pin screw terminals, grid dimension 5,08, Bus: 2 x 2 pin screw terminals, grid dimension 3,81
Supply 18… 35VDC
Current consumption max. 350 mA at 24VDC
Inputs 8 x S0 class A according to EN 62053-31
S0 voltage 18V open circuit
S0 line current 8 x approx.17 mA max.
Active input IS0 > 10mA
Inactive input IS0 < 2mA
Debounce time approx. 8 msec
Temperature range -10 °C to -55 °C
Baud rates 300, 2400, 9600 bit/s (default: 2400 bit/s)
Bus load 1 unit load (approx. 1,5mA)
Number of logical 4M bus slaves 4
Slave function 8 x counter, 32Bit dual

Variant



  • BCM 8 M-Bus   Item number: 003164 Pulse acquisition module for up to eight S0 pulse counters
    and conversion of pulse readings into M-Bus protocol

intelligente-gateways-signalkonverter-ankopplung-messgeraete-bip-iv-modul

LoRaWAN-Gateway Outdoor

The LoRaWAN gateway is designed for outdoor use and enables wireless connection of LoRAWAN sensors (nodes). The gateway includes an SX1301 LoRaWAN concentrator, which offers
provides 10 programmable parallel demodulation paths.

Features

  • Connection of LoRaWAN sensors
  • SX1301 LoRaWAN Concentrator
  • IP65 protection class
  • incl. fiber optic antenna

Technical Data

Radio frequency 868 MHz
Power supply PoE or external plug-in power supply 230/12 VDC
Antenna external fiber optic antenna for LoRa RF
Connection TCP/IP (RJ 45)
Protection class IP 65 outdoor gateway

Variant



  • LoRaWAN-Gateway Outdoor   Item number: 004900 Radio frequency: 868 MHz
    Power supply: PoE or external plug-in power supply 230/12 VDC
    Antenna: external fiber optic antenna for LoRa RF
    Connection: TCP/IP (RJ 45)
    Protection class: IP 65 outdoor gateway


BIP IV Modul

The BIP IV is an intelligent gateway and enables the coupling of the measuring devices of the UBN series, the energy meters BME as well as devices with Modbus RTU protocol to the Profibus. The interface has a Profibus-DP standard interface according to EN50170 based on the intelligent Profibus controller SPC3 and another RS485 interface, the device bus.

Features

  • Profibus gateway for coupling devices of the UBN series and energy meters of the BME series via Modbus RTU
  • Subnetwork of up to 32 Modbus participants possible
  • Communication variant: Profibus DP
  • DIN rail mounting according to IEC 60715
  • 3 TE width

Technical Data

Case Insulated plastic case for DIN-rail mounting type DIN EN 50022 (TS35)
Protection class IP 20 for front panel and IP 20 for terminals
Temperature range Surrounding temperature -10°C to 55°C
Storage temperature -20°C to 60°C
Power supply 18..35VDC / 50mA
Connection elements Screw terminals (type K) for conductors up to 4 mm2 according to VDE 0100 and VGB 4
Weight approx. 80g
Interfaces Profibus SUB-D 9pol. according to EN 50170, baud rates up to 12MBit/s

RS 485 (device bus) for encoder connection

The interfaces are electrically isolated from each other

Assignment of the decentralized periphery 32 byte inputs, 32 byte outputs
Transmission rates 9600 bit/s for devices type code 1-5

19200 bit/s bit/s for devices type code 6
(Modbus RTU) and type code 7 ( meter BME)

Variant



  • BIP IV Modul   Item number: 004356 Berg interface for Profibus (4th generation)
    for integration of BME Modbus meters
    or UBN network analyzers to the
    Siemens Profibus DP


  • BIP-MANAGER TIA   Item number: 004385 Preprogrammed TIA function block for a
    S7-1200/1500 controller for the readout of measuring data
    of the Berg measuring devices connected to the BIP IV


  • BIP-MANAGER V4   Item number: 002694 Preprogrammed STEP-7 function block for a
    S7-300/400 controller for the readout of measurement data
    of the Berg measuring devices connected to the BIP IV

BAC2 Analog Meter

The BAC2 module is a 2-channel high-resolution measuring module for analog values and designed for passive 2-wire transmitters 4-20mA (flow, temperature, humidity, pressure, level, etc.) or active measuring signals 0(4)-20mA. When using passive 2-wire transmitters, the supply of the transmitters is done by the BAC2.

Features

  • Profibus gateway for coupling devices of the UBN series and energy meters of the BME series via Modbus RTU
  • Subnetwork of up to 32 Modbus participants possible
  • Communication variant: Profibus DP
  • DIN rail mounting according to IEC 60715
  • 3 TE width

Technical Data

Case: Insulated plastic case for DIN-rail mounting type DIN EN 50022 (TS35)
Protection class: IP 20 for front panel and IP 20 for terminals
Dimensions: W:53 mm (3HP), H:90 mm, D:58 mm (without Profibus connector)
Power supply: 24VDC +/- 5% approx. 100mA
Connecting elements: screw terminals for conductors up to max. 4 mm2
Weight: approx. 90g
Analog inputs: 2, potential separated, but not among each other
Measuring range: 2 x 0(4)-20mA
Internal load: 102.4 Ohm, adjustable
Sensor supply: approx. 22V channel, current limited to 27..28mA (short circuit proof)
Resolution: 15Bit (32767 counts), normalized by software to 0..10000
Sample rate: 5 / sec
Nonlinearity: 10ppm full scale range
Temperature drift: -13ppm/°C,measured in ambient temperature range 20-50°C
Energy meter: 2 x 32Bit
Real time clock: battery buffered, accuracy 3.5ppm
Load profile memory: memory size 4 Megabyte, sufficient for approx. 262.000 records
Data interface: RS485, protocol Modbus RTU

Variant



  • BIP IV Modul   Item number: 004356 Berg interface for Profibus (4th generation)
    for integration of BME Modbus meters
    or UBN network analyzers to the
    Siemens Profibus DP


  • BIP-MANAGER TIA   Item number: 004385 Preprogrammed TIA function block for a
    S7-1200/1500 controller for the readout of measuring data
    of the Berg measuring devices connected to the BIP IV


  • BIP-MANAGER V4   Item number: 002694 Preprogrammed STEP-7 function block for a
    S7-300/400 controller for the readout of measurement data
    of the Berg measuring devices connected to the BIP IV


Fragen Sie uns!
Unser zuständiger Ansprechpartner ruft Sie gern zurück und beantwortet Ihre Fragen. Bitte wählen Sie einen Themenbereich, zu dem Sie ganz individuell beraten werden möchten.
Für die Verarbeitung Ihrer personenbezogenen Daten gilt unsere Datenschutzerklärung.
Just Ask Us
Our responsible contact person will be happy to call you back and answer your questions. Please select a subject area on which you would like to receive individual advice.
The processing of your personal data is governed by our Datenschutzerklärung.