berg - die Energieoptimierer

Gateways and Signal Converters

multicountermodul-fuer- datenuebertragung-gateways-signalkonverter-bcm4m-bus

BCM 4 M-Bus

For combined acquisition of four S0 pulse counters and machine running times. The multicounter module is designed for data transmission in M-Bus format.

Features

  • Counter module with four separate S0 channels according to EN 62053-31
  • Communication variant: M-Bus
  • DIN rail mounting according to IEC 60715
  • 3 module width
  • Suitable for contacts and open collector transistors
  • Channels programmable for counting machine running times

Technical data

Casing In acc. with DIN 43880, self-extinguishing PPO
Dimensions (W × H × D) in mm W: 53 mm (3 module width), H: 90 mm (incl. connector), D: 58 mm
Installation DIN profile rail according to EN 50022
Protection class IP 20
Connectors S0 inputs: 1× 8-pole screw terminals, grid dimension 5.08, bus: 2× 2-pole screw terminals, grid dimension 3.81
Power supply 24 V DC ±5%
Power consumption max. 60 mA
Inputs 4× S0 Class A acc. to EN 62053-31
S0 voltage 15.5 V idle
S0 line current 4× approx. 14 mA max.
Input IS0 > 10 mA Input IS0 > 10 mA
Active IS0 < 2 mA
Debounce time Approx. 8 ms
Temperature range –10°C…–55°C
Baud rates 300, 2,400, 9,600 bps (default: 2,400 bps)
Bus load 1 unit load (approx. 1.5 mA)
Number of logical 4 M-Bus slaves 4
Slave-function 4× counter, 32 bit dual
Max. counting frequency 50 Hz
Data transfer M-Bus acc. to EN 1434

Download

Variant



  • BCM 4 M-Bus   Item number: 003773 Pulse acquisition module for up to four S0 pulse counters
    and conversion of pulse readings into M-Bus protocol

BCM 8 DP

S0 impulse acquisition module for transmission of consumption values from up to eight intermediate meters into the Profibus DP protocol.

Features

  • Counter module with eight separate S0 channels according to EN 62053-31
  • Communication variant: ProfibusDP
  • DIN rail mounting according to IEC 60715
  • 6 module width
  • Suitable for contacts and open collector transistors
  • Channels programmable for counting machine running times (model-dependent)

Technical data

Case Acc. to DIN 43880, self-extinguishing PPO
Dimensions (W × H × D) in mm W: 106 mm (6 module width), H: 115 mm (incl. connector), D: 63 mm
Installation DIN profile rail acc. to EN 50022
Protection Class IP 20
Connections S0 inputs: 2× 8-pin screw terminals, grid dimension 5.08, bus: 2× 2-pin screw terminals, grid dimension 3.81
Supply 18…35 V DC
Current consumption Max. 350 mA at 24 V DC
Inputs 8× S0 class A acc. to EN 62053-31
S0 voltage 18 V open circuit
S0 line current 8× approx.17 mA max.
Active input IS0 > 10 mA
Inactive input IS0 < 2 mA
Debounce time Approx. 8 ms
Temperature range –10…–55°C
Baud rates 300, 2,400, 9,600 bps (default: 2,400 bps)
Bus load 1 unit load (approx. 1.5 mA)
Number of logical 4 M-Bus slaves 4
Slave function 8× counter, 32 bit dual
Max. meter frequency 50 Hz
Data transmission S0 to ProfibusDP
Data interface Profibus DP, SUB-D 9 pol. acc. to EN 50170,
Baud rates Up to 12 Mbaud
DP allocation 32 byte E-periphery, 32 byte A-periphery

Variant



  • BCM 8 Profibus DP   Item number: 000595 Pulse acquisition module for up to eight S0 pulse counters
    and conversion of the pulse states into the Profibus DP protocol
S0-impulserfassungsmodul-zur-uebertragung-von-verbrauchswerten-gatewyas-signalkonverter-bcm-8dp


multicountermodul-fuer-datenuebertragung-ModbusRTU-gateways-signalkonverter-bcm-8modbus

BCM 8 Modbus

For combined acquisition of S0 impulse counters and machine running times. The multicounter module is designed for data transmission in the ModbusRTU protocol.

Features

  • Counter module with eight separate S0 channels according to EN 62053-31
  • Communication variant: Modbus RTU
  • DIN rail mounting according to IEC 60715
  • 6 module width
  • Suitable for contacts and open collector transistors
  • Channels programmable for counting machine running times (model-dependent)

Technical data

Case Acc to. DIN 43880, self-extinguishing PPO
Dimensions (W × H × D) in mm W: 106 mm (6 modules), H: 115 mm (incl. connector), D: 63 mm
Installation DIN profile rail acc. to EN 50022
Protection class IP 20
Connections S0 inputs: 2× 8-pin screw terminals, grid dimension 5.08, bus: 2× 2-pin screw terminals, grid dimension 3.81
Supply 18…35 V DC
Current consumption Max. 350 mA at 24 V DC
Inputs 8× S0 class A acc. to EN 62053-31
S0 voltage 18 V open circuit
S0 line current 8× approx. 17 mA max.
Active input IS0 > 10 mA
Inactive input IS0 < 2 mA
Debounce time Approx. 8 ms
Temperature range –10…–55°C
Baud rates 300, 2,400, 9,600 bps (default: 2,400 bps)
Bus load 1 unit load (approx. 1.5 mA)
Number of logical 4 M-Bus slaves 4
Slave function 8× counter, 32 bit dual
Max. Counter frequency 50 Hz
Data transmission S0/machine run times on Modbus RTU
Data formats DWORD (32 bit dual), real single precision
Baud rates 300…57.6 k
Transmission media RS485, connection via screw terminals
Termination Fail-safe, can be switched on/off via jumper

 

Variant



  • BCM 8 Modbus   Item number: 002639 Pulse acquisition module for up to eight S0 pulse counters
    and conversion of the pulse states into the Modbus RTU protocol.

BCM 8 M-Bus

For combined acquisition of 8 S0 impulse counters and machine running times. The multicounter module is designed for data transmission in M-Bus format.

Features

  • Counter module with eight separate S0 channels according to EN 62053-31
  • Communication variant: M-Bus
  • DIN rail mounting according to IEC 60715
  • 6 module width
  • Suitable for contacts and open collector transistors
  • Channels programmable for counting machine running times (model-dependent)

Technical data

Case Acc. to DIN 43880, self-extinguishing PPO
Dimensions (W × H × D) in mm W: 106 mm (6 module width), H: 115 mm (incl. connector), D: 63 mm
Installation On DIN profile rail acc. to EN 50022
Protection class IP 20
Connections S0 inputs: 2× 8-pin screw terminals, grid dimension 5.08, bus: 2× 2-pin screw terminals, grid dimension 3.81
Supply 18…35 V DC
Current consumption Max. 350 mA at 24 V DC
Inputs 8× S0 class A acc. to EN 62053-31
S0 voltage 18 V open circuit
S0 line current 8× approx. 17 mA max.
Active input IS0 > 10 mA
Inactive input IS0 < 2 mA
Debounce time Approx. 8 ms
Temperature range –10…–55°C
Baud rates 300, 2,400, 9,600 bps (default: 2,400 bps)
Bus load 1 unit load (approx. 1.5 mA)
Number of logical 4 M-Bus slaves 4
Slave function 8× counter, 32 bit dual

 

Variant



  • BCM 8 M-Bus   Item number: 003164 Pulse acquisition module for up to eight S0 pulse counters
    and conversion of pulse readings into M-Bus protocol
S0-impulszähler-erfassung-gateways-signalkonverter-bcm-8m-bus


LoRaWAN-Gateway Outdoor

The LoRaWAN gateway is designed for outdoor use and enables wireless connection of LoRAWAN sensors (nodes). The gateway includes an SX1301 LoRaWAN concentrator that provides ten programmable parallel demodulation paths.

Features

  • Connection of LoRaWAN sensors
  • SX1301 LoRaWAN concentrator
  • IP 65 protection class
  • Incl. fiber optic antenna

Technical data

Radio frequency 868 MHz
Power supply PoE or external plug-in power supply 230/12 V DC
Antenna External fiber optic antenna for LoRa RF
Connection TCP/IP (RJ 45)
Protection class IP 65 outdoor gateway
Dimensions (W × H × D) in mm 490 × 120 × 190

 

Variants



  • LoRaWAN-Gateway Outdoor   Item number: 004900 Radio frequency: 868 MHz
    Power supply: PoE or external plug-in power supply 230/12 VDC
    Antenna: external fiber optic antenna for LoRa RF
    Connection: TCP/IP (RJ 45)
    Protection class: IP 65 outdoor gateway


BIP IV Modul

The BIP IV is an intelligent gateway and enables the coupling of the measuring devices of the UBN series, the BME energy meters, and devices with Modbus RTU protocol to the Profibus. The interface has a Profibus-DP standard interface according to EN 50170 based on the intelligent Profibus controller SPC3 and another RS485 interface, the device bus.

Features

  • Profibus gateway for coupling UBN series devices and BME series energy meters using the Modbus RTU
  • Subnetwork of up to 32 Modbus components possible
  • Communication variant: Profibus DP
  • DIN rail mounting according to IEC 60715
  • 3 module width

Technical data

Case Insulated plastic case for DIN rail mounting type DIN EN 50022 (TS35)
Protection class IP 20 for front panel and IP 20 for terminals
Temperature range Surrounding temperature –10°…55°C
Storage temperature –20…60°C
Power supply 18…35 V DC/50 mA
Connection elements Screw terminals (type K) for conductors up to 4 mm2 acc. to VDE 0100 and VGB 4
Weight Approx. 80 g
Interfaces Profibus SUB-D 9 pol. acc. to EN 50170, baud rates up to 12 Mbps

RS 485 (device bus) for encoder connection

The interfaces are electrically isolated from each other

Assignment of the decentralized periphery 32 bit inputs, 32 bit outputs
Transmission rates 9,600 bps for devices type code 1 to 5

19,200 bps for devices type code 6
(Modbus RTU) and type code 7 (meter BME)

 

Variants



  • BIP IV Modul   Item number: 004356 Berg interface for Profibus (4th generation)
    for integration of BME Modbus meters
    or UBN network analyzers to the
    Siemens Profibus DP


  • BIP-MANAGER TIA   Item number: 004385 Preprogrammed TIA function block for a
    S7-1200/1500 controller for the readout of measuring data
    of the Berg measuring devices connected to the BIP IV


  • BIP-MANAGER V4   Item number: 002694 Preprogrammed STEP-7 function block for a
    S7-300/400 controller for the readout of measurement data
    of the Berg measuring devices connected to the BIP IV
intelligente-gateways-signalkonverter-ankopplung-messgeraete-bip-iv-modul


hochauflösendes-messmodul-fuer-Analogwerte-gateways-signalkonverter-bac2-analogzaehler

BAC2 Analog Meter

The BAC2 module is a two-channel high-resolution measuring module for analog values and designed for passive 2-wire transmitters 4 mA to 20mA (flow, temperature, humidity, pressure, level, etc.) or active measuring signals 0(4) mA to 20mA. When using passive 2-wire transmitters, the supply of the transmitters is done by the BAC2.

Features

  • Profibus gateway for coupling UBN series devices and BME series energy meters using the Modbus RTU
  • Subnetwork of up to 32 Modbus components possible
  • Communication variant: Profibus DP
  • DIN rail mounting according to IEC 60715
  • 3 module width

Technical data

Case: Insulated plastic case for DIN rail mounting type DIN EN 50022 (TS35)
Protection class: IP 20 for front panel and IP 20 for terminals
Dimensions (W × H × D) in mm W: 53 mm (3 module width), H: 90 mm, D: 58 mm (without Profibus connector)
Power supply: 24 V DC ±5% approx. 100 mA
Connecting elements: Screw terminals for conductors up to max. 4 mm2
Weight: Approx. 90 g
Analog inputs: 2, potential separated, but not among each other
Measuring range: 2× 0(4)…20 mA
Internal load: 102.4 Ω, adjustable
Sensor supply: Approx. 22 V channel, current limited to 27…28 mA (short circuit proof)
Resolution: 15 bit (32,767 counts), normalized by software to 0…10,000
Sample rate: 5/s
Nonlinearity: 10 ppm full scale range
Temperature drift: –13 ppm/°C, measured in ambient temperature range 20…50°C
Energy meter: 2× 32 bit
Real-time clock: Battery buffered, accuracy 3.5 ppm
Load profile memory: Memory size 4 MB, sufficient for approx. 262,000 records
Data interface: RS485, protocol Modbus RTU

 

Variants



  • BAC2 M-Bus   Item number: 004413 Module for integration of two 4…20mA signals to one consumption value
    Data transmission in M-Bus format


  • BAC2 Modbus   Item number: 004412 Module for integration of two 4…20mA signals to one consumption value
    Data transmission in Modbus RTU bus format

Fragen Sie uns!
Unser zuständiger Ansprechpartner ruft Sie gern zurück und beantwortet Ihre Fragen. Bitte wählen Sie einen Themenbereich, zu dem Sie ganz individuell beraten werden möchten.
Für die Verarbeitung Ihrer personenbezogenen Daten gilt unsere Datenschutzerklärung.
Just Ask Us
Our responsible contact person will be happy to call you back and answer your questions. Please select a subject area on which you would like to receive individual advice.
The processing of your personal data is governed by our Datenschutzerklärung.